Cat6 vs Cat6A for an office or warehouse fit-out.
Cat6 carries 1 gigabit to every outlet at up to 100 metres, which is what most desks, phones and cameras use. Cat6A carries 10 gigabit over the same 100 metres, and it is worth specifying for access points, links between cabinets and any ceiling you do not want to reopen.
- Sheet
- Guide
- Published
- 30 September 2026
- Last updated
- 30 September 2026
- Written by
- Gentex AU
Cat6 vs Cat6A, row by row.
Figures are the published limits of the cabling and Ethernet standards, for a full link with patch leads included.
- Rated frequency
- Cat6: 250 MHz
- Cat6A: 500 MHz
- 1 gigabit
- Cat6: Up to 100 metres
- Cat6A: Up to 100 metres
- 2.5 and 5 gigabit
- Cat6: Up to 100 metres
- Cat6A: Up to 100 metres
- 10 gigabit
- Cat6: Up to 37 metres. From 37 to 55 metres it depends on interference from neighbouring cables
- Cat6A: Up to 100 metres
- Power over Ethernet
- Cat6: Carries it. Runs warmer in a large bundle
- Cat6A: Carries it. The category recommended for high-power PoE
- Cable
- Cat6: Thinner, bends tighter, quicker to terminate
- Cat6A: Thicker, stiffer, slower to terminate
The 10 gigabit row is the one that matters. Cat6 was not written for 10 gigabit. The guidance for running it on existing Cat6 is that it should work to 37 metres, and from there to 55 metres it depends on how much signal leaks between cables bundled together. Nobody knows which side of that line a link falls on until it is tested.
Cat6A was written for 10 gigabit at the full 100 metres. That is the whole difference, and everything else on this page follows from it.
When Cat6A is worth it.
- 01 The cable to an access point.
- Many current Wi-Fi access points have ports faster than 1 gigabit, and the cabling guidance for new installations recommends Cat6A to them. The access point will be replaced before the cable is. If you are planning business Wi-Fi, this is the first place to spend.
- 02 Links between cabinets.
- The run from the main rack to a second cabinet carries everything plugged into that cabinet. Where it is under 100 metres, Cat6A keeps it at 10 gigabit. Where it is over, no copper category will do it: the run needs fibre or an intermediate cabinet.
- 03 10 gigabit to the desk.
- Few desks need it. The ones that do move large files to a server on site: video, drawings, imaging. If that describes four desks, run Cat6A to those four.
- 04 High-power PoE.
- A single cable can now carry up to 90 watts of power. Power heats the cable, more so in a large bundle, and Cat6A is the category recommended for that load.
- 05 A ceiling you do not want to reopen.
- Behind set plaster, above a finished fit-out, or in a tenancy you have to make good, the cable has to outlast several generations of equipment. The labour to pull it is spent once. Choose the cable that will not need pulling again.
When Cat6 is the right answer.
- Desks where the work is email, phones, accounts and a browser. 1 gigabit is more than those use.
- Fixed cameras, door controllers and readers. Each uses a small fraction of a gigabit.
- An open warehouse tray or a ceiling grid, where adding a cable later is a small job.
- Cat6 that is already in the building and tests clean. Keep it and spend the money on the new runs.
A workable rule: Cat6A to access points, between cabinets and above any ceiling you cannot reopen. Cat6 to the desk and the camera unless one has a stated reason.
What else changes.
The cost difference between the two is not only the price of the cable. These are the drivers, without numbers, because the numbers come from your building.
- 01 Containment fills sooner.
- Cat6A is a thicker cable. The same tray, conduit or wall cavity holds fewer of them, and a conduit sized for Cat6 may not take the Cat6A count. On a warehouse job, where the containment is the larger part of the work, that matters more than the cable.
- 02 Bends need more room.
- A stiffer cable needs a wider bend behind the outlet and into the back of the patch panel. Shallow wall boxes and a full cabinet are where that shows up.
- 03 Termination takes longer.
- Each Cat6A outlet takes longer to terminate than a Cat6 one, and shielded cable also has to be bonded to earth at the rack. Multiply by the outlet count.
- 04 Every part has to match.
- A link performs at the level of its lowest-rated part. Cat6A cable on a Cat6 patch panel or a Cat6 outlet is a Cat6 link, and it will test as one.
- 05 The test is harder to pass.
- A Cat6A link is tested to 500 MHz, not 250. A termination that would scrape through on Cat6 fails, which is the point of paying for it.
A checklist before you accept a cabling quote.
Eight questions. If a quote cannot answer them, it is not yet a quote for your building.
Ask, or answer
- Which outlets will carry more than 1 gigabit during the life of the fit-out?
- Where do the access points go, and what speed are their ports?
- How long is the longest run, and does any pass 100 metres?
- Which devices take their power from the cable, and how much?
- Can the ceiling be opened again without a builder?
- Is there room left in the tray, the conduit and the rack?
- Does the quote name the category of the cable, the outlets and the patch panel, not only the cable?
- Is every link tested, and do you receive the results?
Site attendance and the itemised quote are at no charge. The cable category is named in it.
The category is one line in a cabling job. The containment, the rack, the labelling and the UPS are covered on our data cabling page, along with what is handed over when the job is commissioned.
If the cable is already in, send us what is printed on its sheath and a photo of the patch panel. We will say whether it is worth keeping before anyone quotes to replace it. That assessment is part of a data cabling site visit, which is at no charge.
Questions we get asked.
Can Cat6 run 10 gigabit?
Is Cat6A worth it for a small office?
Are all Cat6 cables the same?
Can Cat6 and Cat6A be mixed in one building?
Related sheets.
- Data cabling, racks and UPS What a cabling job includes, how it runs and what is handed over at the end.
- Business Wi-Fi and networking The access points and PoE switches that decide how fast the ceiling cable needs to be.
- Solutions: everything we install The cameras, doors and screens that each need an outlet on the same plan.
- Guide: what a commercial security system costs The cost drivers for the systems that plug into the cabling, set out the same way.
Send us the outlet count.
A floor plan with the outlets and access points marked is enough for us to say where Cat6A earns its place. We are based in Tullamarine and enquiries are read Monday to Friday, 07:00–16:00.
- To
- Gentex AU · Tullamarine VIC
- Reply
- Phone or email, usually the same business day
- Attending
- Mon–Fri 07:00–16:00
- Licensing
- Victorian Private Security Licence